Diesel Engine Controller
Product Details:
- Display LED
- Sensor Type POTENTIAL FREE CONTACT
- Frequency 50 Hertz (HZ)
- Application FIRE HYDRANT PUMP
- Supply Voltage 230VAC Volt (v)
- Dimension(L*W*H) 151 X 151 Millimeter (mm)
- Weight 500 Milligram (mg)
- Click to View more
Price And Quantity
- 1 Piece
- 8500 INR/Piece
Product Specifications
- 230VAC Volt (v)
- FIRE HYDRANT PUMP
- 50 Hertz (HZ)
- 1 YEAR
- POTENTIAL FREE CONTACT
- LED
- 500 Milligram (mg)
- 151 X 151 Millimeter (mm)
Trade Information
- 1 Piece Per Day
- 2-3 Days
- If order is confirmed we will reimburse the sample cost
- All India
Product Description
Our company has sculpted a remarkable place in the market as a reputed manufacturer and supplier of Automative Diesel Engine Controller. It is highly reliable & compact microcontroller based engine crank relay system. This system offers annunciation and controlling with audio / visual signal & potential free o/p contact. We manufacture this controller at our sound production unit using high quality materials and components. Automative Diesel Engine Controller is available in different specifications as per their requirements.
Features:
- Compact design
- Easy to install
- Maintenance free
Diesel Engine Controller
Introduction -
Dynatek make ECR 16 is one of the most user friendly, Highly reliable & compact microcontroller based Engine Crank Relay system. This system offers annunciation and controlling with Audio / Visual signal & potential free o/p contact. It has Auto / Manual mode.
ECR 16" Controller is developed to start engine in Auto / Manual mode. In auto mode Controller continuously scan "HYDRANT PRESSURE", if it drops Controller cranks engine automatically through start relay .When engine reaches to set running condition it is automatically switched over to manual mode to stop the engine manually as per the "FIRE FIGHTING NORMS". It accepts input faults (Potential free Contact) like LLOP, Over speed, Over heat, etc. Any one of the input fault occurs, the corresponding LED window starts flashing & gives signal to hooter relay for audio alarm. Hooter relay is provided to connect hooter for audio alarm. Input faults are site selectable ( NO & NC). Dual rate flashing is provided for differentiating the first & subsequent fault. Setting for ON TIME, OFF TIME & Attempt for CRANK can be done by DIP SWITCH
- Low Lub Oil Pressure 2) High Water Temperature 3) Over Speed
- Low Diesel level 5) Engine fail to start
Fault Input Points | - | 12 Nos. ( All the inputs are opto - isolated) |
---|---|---|
Power Consumption | - | 4 Watt |
Weight - | - | 300 gm. |
Window indication | - | Bright Red LED Display |
Fault Inputs | - | Potential free contact : NO or NC |
Flashing rate | - | For first fault 300 flashes / Min. & Subsequent fault 60 flashes / Min. |
Hooter Relay contact Rating | - | 1 Amp. / 230 VAC It is advisable to connect additional relay for heavy load |
START, STOP Relay contact Rating | - | 10 Amp. / 230 VAC It is advisable to connect additional relay for heavy load. |
Additional open collector o/p for Remote Indication | - | 100 mA Sinking mode |
Supply | - | 24 / 12 VDC. |
Mechanical Details Bezel Size Cut out Size |
- | 155 X 155 mm 138 X 138 mm |
Dynatek Instruments Private Limited
All Rights Reserved.(Terms of Use) Developed and Managed by Infocom Network Private Limited. |